  Rated insulation voltage (Ui) Rated operational voltage (Ith) No. of built-in elements (circuits) Power supply voltage fluctuation Withstand voltage Lightning impulse Output contact rating Insulation resistance Operating time Shock resistance Vibration resistance Operating temperature Storing temperature Altitude
(L-A) (L-A)
CAX-021 250V AC/DC 100/110V DC
(For indication: 24V DC)
12 elements 100/110 V DC: -20 to +30%, 24 V DC: ±10%, 100/110 V AC: ±15% 2,000V AC for one minute ±4,500V, 3 times for each pole (1.2/50μs) 125V DC, 1A (3A max. in total via common bus) 10MΩ or more (500 V DC Megger) See each timing chart. 300m/s2, 3 times in each direction 16.7 Hz, 0.4 mm double amplitude, Vibration time: 600s -10 to 55℃ -20 to 60℃ 2,000m max.
CAX-031
CAX-032
250V AC/DC 100/110V DC 5 elements 100/110 V DC: -20 to +30%, 24 V DC: ±10%, 100/110 V AC: ±15% 2,000V AC for one minute ±4,500V, 3 times for each pole (1.2/50μs) 125V DC, 1A (3A max. in total via common bus) 10MΩ or more (500 V DC Megger) See each timing chart. 300m/s2, 3 times in each direction 16.7 Hz, 0.4 mm double amplitude, Vibration time: 600s -10 to 55℃ -20 to 60℃ 2,000m max.
CAX-041 250V AC/DC 100/110V DC 8 elements 100/110 V DC: -20 to +30%, 24 V DC: ±10%, 100/110 V AC: ±15% 2,000V AC for one minute ±4,500V, 3 times for each pole (1.2/50μs) 125V DC, 1A (3A max. in total via common bus) 10MΩ or more (500 V DC Megger) See each timing chart. 300m/s2, 3 times in each direction 16.7 Hz, 0.4 mm double amplitude, Vibration time: 600s -10 to 55℃ -20 to 60℃ 2,000m max.
CAX-051 250V AC/DC 100/110V DC
(For indication: 24V DC)
11 elements 100/110 V DC: -20 to +30%, 24 V DC: ±10%, 100/110 V AC: ±15% 2,000V AC for one minute ±4,500V, 3 times for each pole (1.2/50μs) 125V DC, 1A (3A max. in total via common bus) 10MΩ or more (500 V DC Megger) See each timing chart. 300m/s2, 3 times in each direction 16.7 Hz, 0.4 mm double amplitude, Vibration time: 600s -10 to 55℃ -20 to 60℃ 2,000m max.
CAX-061 250V AC/DC 100/110V DC 5 elements 100/110 V DC: -20 to +30%, 24 V DC: ±10%, 100/110 V AC: ±15% 2,000V AC for one minute ±4,500V, 3 times for each pole (1.2/50μs) 125V DC, 1A (3A max. in total via common bus) 10MΩ or more (500 V DC Megger) See each timing chart. 300m/s2, 3 times in each direction 16.7 Hz, 0.4 mm double amplitude, Vibration time: 600s -10 to 55℃ -20 to 60℃ 2,000m max.
CAX-071
CAX-072
CAX-073
250V AC/DC 100/110V DC
(CAX-073: 100/110V AC)
(CAX-71)6 elements 100/110 V DC: -20 to +30%, 24 V DC: ±10%, 100/110 V AC: ±15% 2,000V AC for one minute ±4,500V, 3 times for each pole (1.2/50μs) 125V DC, 1A (3A max. in total via common bus) 10MΩ or more (500 V DC Megger) See each timing chart. 300m/s2, 3 times in each direction 16.7 Hz, 0.4 mm double amplitude, Vibration time: 600s -10 to 55℃ -20 to 60℃ 2,000m max.
CAX-081
CAX-082
250V AC/DC 100/110V DC (CAX-81)6 elements
(CAX-82)5 elements
100/110 V DC: -20 to +30%, 24 V DC: ±10%, 100/110 V AC: ±15% 2,000V AC for one minute ±4,500V, 3 times for each pole (1.2/50μs) 125V DC, 1A (3A max. in total via common bus) 10MΩ or more (500 V DC Megger) See each timing chart. 300m/s2, 3 times in each direction 16.7 Hz, 0.4 mm double amplitude, Vibration time: 600s -10 to 55℃ -20 to 60℃ 2,000m max.