NKDB TYPE

FEATURES

No serge, no noise

Serge and noise don't generate because circuit opening and closing don't exist.
This alarm can be used near electronic devices which are sensitive for noise.

Dual output of bell and buzzer sounds

Bell sound for major failure and buzzer sound for minor failure can be output together when 2 failure happens simultaneously.

Test circuit is not necessary

Test circuit is not necessary because test switch is built-in the body.

Small size, lightweight

Small and lightweight body is suitable for every place.

  Rating Performance Normal service condition
Rated operational voltage Volume Power consumption Terminal screw Insulation resistance Power-frequency withstand voltage Impulse withstand voltage Vibration resistance Shock resistance Operating temperature Storing temperature Relative humidity Altitude
NKDB102TA-11 100 / 110V AC / DC (–20% to +30%) 70dB (max.) 5W max.
(no power consumption while ready state)
M4×9 50MΩ or more
(between electric circuit and ground)
2,000V AC (60Hz),
1min (between electric circuit and ground)
±5kV (1.2×50μs),
each 3 time (between electric circuit and ground)
Frequency range: 10 to 55 to 10Hz (each 1min.),
width: 1.5mm,
3 directions 2hours
6 directions, 500m/s2,
each 3 time
–10 to 55℃ –20℃ to 60℃
(no condensation, no freeze)
20 to 80%
(day average, no condensation)
2,000m max.
NKDB112TA-11 100 / 110V AC / DC (–20% to +30%) 70dB (max.) 5W max.
(no power consumption while ready state)
M4×9 50MΩ or more
(between electric circuit and ground)
2,000V AC (60Hz),
1min (between electric circuit and ground)
±5kV (1.2×50μs),
each 3 time (between electric circuit and ground)
Frequency range: 10 to 55 to 10Hz (each 1min.),
width: 1.5mm,
3 directions 2hours
6 directions, 500m/s2,
each 3 time
–10 to 55℃ –20℃ to 60℃
(no condensation, no freeze)
20 to 80%
(day average, no condensation)
2,000m max.
NKDB132TA-11 100 / 110V AC / DC (–20% to +30%) 70dB (max.) 5W max.
(no power consumption while ready state)
M4×9 50MΩ or more
(between electric circuit and ground)
2,000V AC (60Hz),
1min (between electric circuit and ground)
±5kV (1.2×50μs),
each 3 time (between electric circuit and ground)
Frequency range: 10 to 55 to 10Hz (each 1min.),
width: 1.5mm,
3 directions 2hours
6 directions, 500m/s2,
each 3 time
–10 to 55℃ –20℃ to 60℃
(no condensation, no freeze)
20 to 80%
(day average, no condensation)
2,000m max.
NKDB102TA-DC02 24V DC (±10%) 70dB (max.) 5W max.
(no power consumption while ready state)
M4×9 50MΩ or more
(between electric circuit and ground)
2,000V AC (60Hz),
1min (between electric circuit and ground)
±5kV (1.2×50μs),
each 3 time (between electric circuit and ground)
Frequency range: 10 to 55 to 10Hz (each 1min.),
width: 1.5mm,
3 directions 2hours
6 directions, 500m/s2,
each 3 time
–10 to 55℃ –20℃ to 60℃
(no condensation, no freeze)
20 to 80%
(day average, no condensation)
2,000m max.
NKDB132TA-DC02 24V DC (±10%) 70dB (max.) 5W max.
(no power consumption while ready state)
M4×9 50MΩ or more
(between electric circuit and ground)
2,000V AC (60Hz),
1min (between electric circuit and ground)
±5kV (1.2×50μs),
each 3 time (between electric circuit and ground)
Frequency range: 10 to 55 to 10Hz (each 1min.),
width: 1.5mm,
3 directions 2hours
6 directions, 500m/s2,
each 3 time
–10 to 55℃ –20℃ to 60℃
(no condensation, no freeze)
20 to 80%
(day average, no condensation)
2,000m max.