TQS/TQD TYPE CAPACITOR BUILT-IN TERMINAL BLOCK

TQS/TQD TYPE CAPACITOR BUILT-IN TERMINAL BLOCK

FEATURES

Using the wire dropping-off prevention function

The wire dropping-off prevention function has been added to the capacitor built-in terminal block. It saves time for wiring checks.

The size of the TQ-5.5 type has been more compact than conventional models (TCS type)

In conformity with the B-402 power standard, the size of the TQ-5.5 has been further reduced over the TCS type which was miniaturized from the TEC type. The volume reduction ratio is 40%. The width has been reduced from 14 mm to 11 mm.

Unit color differentiation

The terminal block is gray. It can be easily differentiated from conventional black terminal blocks.
* The TQ type uses high-performance engineering plastic resin (modified PPE resin), the same material as conventional models.

Applicable to test tools

As with the conventional model (TCS / TCD type), the TQ type enables easy pressure voltage tests and sequence tests by using test tools.

Using the high-performance film capacitor

The TQS / TQD type terminal blocks incorporate a metalized polypropylene film capacitor that provides high withstand voltage and reliability, anda dielectric material with a self-recovery effect.

Saving wiring with the jumper

The jumper is available as an accessory. It saves time for the wiring step.

Conformable standard : JIS C2811, B-402

Item Rating Performance Standard operating condition
Rated insulation voltage (Ui) Rated impulse withstand voltage Rated current-carrying capacity (Ith) Applicable wire size Screw size Applicable crimp terminal Power-frequency withstand voltage Impulse withstand voltage Ambient temperature Storing temperature Altitude
TQS-5.5C
TQS-5.5
600V AC/DC 6,000V 30A 2 to 5.5mm2 M4×8.5 R2-4/
R3.5-4/
R5.5-4
1 minute at 2,500V AC ±7.2kV/3 times for each pole (1.2/50μs) -25 to 50℃ -40 to 75℃ 2,000m max.
TQS-8C
TQS-8
600V AC/DC 6,000V 40A 3.5 to 8mm2 M5×11 R3.5-5/
R5.5-5/
R8-5
1 minute at 2,500V AC ±7.2kV/3 times for each pole (1.2/50μs) -25 to 50℃ -40 to 75℃ 2,000m max.
TQD-8C
TQD-8
600V AC/DC 6,000V 40A 3.5 to 8mm2 M5×11 R3.5-5/
R5.5-5/
R8-5
1 minute at 2,500V AC ±7.2kV/3 times for each pole (1.2/50μs) -25 to 50℃ -40 to 75℃ 2,000m max.
TQS-14C
TQS-14
600V AC/DC 6,000V 60A 5.5 to 14mm2 * M5×11 R5.5-5/
R8-5/
R14-5
1 minute at 2,500V AC ±7.2kV/3 times for each pole (1.2/50μs) -25 to 50℃ -40 to 75℃ 2,000m max.
TQD-14C
TQD-14
600V AC/DC 6,000V 60A 5.5 to 14mm2 * M5×11 R5.5-5/
R8-5/
R14-5
1 minute at 2,500V AC ±7.2kV/3 times for each pole (1.2/50μs) -25 to 50℃ -40 to 75℃ 2,000m max.

* The dropping-off prevention rib is effective for wires 8 mm2 or larger in size.

product document data type volume of data date of update download
TQS/TQD TYPE Capacitor built-in terminal block Catalog PDF 925.0KB - download