FUSE HOLDER
FEATURES
Conformed to JIS C 8314, C8352, and JEM1103.
Both air clearance and creepage distance for insulation in JEM standard 1103 (1976) "insulation distance for controllers" are conformed to rated insulation voltage of 600 V AC / DC in the bear crimp condition (250 V AC or DC for F-10 type).
Excellent heat resistance
For the insulation base of 30 A or more, high-performance engineering plastic is used. It assures high heat resistance and keeps normal condition even if it is left in a furnace of 150°C for 5 hours. Sufficient safety is assured against a temperature increase due to overcurrent.
Light weight and high rigidity
Sufficient strength is retained against rough handling to assure comfortable use. This fuse holder is highly resistant against shock and vibrations to hold the fuse in place.
Rated insulation voltage (Ui) | Rated current-carrying capacity (Ith) | Max. wire size | Screw size | Applicable fuse | Withstand voltage | Lightning impulse | Operating temperature | Temperature increase (at rated current) |
Heat resistant performance | Insulation resistance (1,000 MV DC) |
|
---|---|---|---|---|---|---|---|---|---|---|---|
F-10 | 250V | 10A | 5.5mm2 | M4×8 | 10A (φ6.4×30mm) |
1 minute at 2,500V AC | ±7kV/3 times for each pole (1.2/50μs) | -20 to 50℃ | 35K | 70℃ 5H OK | 1,000MΩmin. |
PF-34 PF-34S |
600V | 30A | 14mm2 | M4×10 | 30A (φ15×50mm) |
1 minute at 2,500V AC | ±7kV/3 times for each pole (1.2/50μs) | -40 to 70℃ | 35K | 150℃ 5H OK | 1,000MΩmin. |
PF-35 PF-35S |
600V | 30A | 14mm2 | M5×12 | 30A (φ15×50mm) |
1 minute at 2,500V AC | ±7kV/3 times for each pole (1.2/50μs) | -40 to 70℃ | 35K | 150℃ 5H OK | 1,000MΩmin. |
DF-34 | 600V | 30A | 14mm2 | M4×10 | 30A (φ15×50mm) |
1 minute at 2,500V AC | ±7kV/3 times for each pole (1.2/50μs) | -40 to 70℃ | 35K | 150℃ 5H OK | 1,000MΩmin. |
DF-35 | 600V | 30A | 14mm2 | M5×12 | 30A (φ15×50mm) |
1 minute at 2,500V AC | ±7kV/3 times for each pole (1.2/50μs) | -40 to 70℃ | 35K | 150℃ 5H OK | 1,000MΩmin. |
NF-61 NF-61S |
600V | 60A | 22mm2 | M5×10 | 30A (φ20×57mm) |
1 minute at 2,500V AC | ±7kV/3 times for each pole (1.2/50μs) | -40 to 70℃ | 35K | 150℃ 5H OK | 1,000MΩmin. |
NF-62 NF-62S |
600V | 60A | 22mm2 | M5×10 | 60A (φ20×75mm) |
1 minute at 2,500V AC | ±7kV/3 times for each pole (1.2/50μs) | -40 to 70℃ | 45K | 150℃ 5H OK | 1,000MΩmin. |
product | document | data type | volume of data | date of update | download |
---|---|---|---|---|---|
FUSE HOLDER | Catalog | 1093.1KB | - | download |